2002G1 | Saf-D-Grid® 400 Receptacle Housing
Product Description
- Saf-D-Grid® 400 Flush Mount Receptacle Housing with snap-in panel mount for 0.8mm panel thickness.
- Flush snap-in panel mount design is compatible with crimp wire contacts.
- First Mate, Last Break ground contact provides the safety of an earthing path before engagement of the power contacts.
- The connectors are rated for current interruption for both electronic (capacitive) and electrical (resistive) loads.
- Passes UL & IEC finger probe (plug & receptacle) and 3mm probe tests (receptacle). Minimizes the risk of personal contact with a hazardous voltage.
- Housings contain the arc if connectors are mated or unmated while under load minimizing risk to personnel.
- Anderson Power Products®® has lead the connector industry in development of DC power connection solutions since the introduction of the SB® electrical connector in 1953. Saf-D-Grid® builds on the proven contact technology used in SB® and Powerpole® connectors by offering features required in 380-400VDC power distribution systems.
- APP® introduced the Saf-D-Grid® connector system in January 2009 as a safe appliance power connector for server, telecommunication, and other devices up to 600 VDC.
- The APP® Saf-D-Grid® plug and receptacle provide for thedirect connection of DC electronic devices to a DC micro-gridpowered by renewable energy or high efficiency DC sources.The connector meets international safety requirements for hazardous, low voltage applications including UL 950 and IEC60950. The Saf-D-Grid® is size compatible with the IEC 320C13 and C14 AC connection system. It is the only connector system so sized that is UL rated for disconnect of a 400 VDC,20 amp load.
- Saf-D-Grid® also enables greater power density by allowing up to 40A and 600V DC or AC within the same space of the IEC320 C13 & C14 system that is limited to 10A and 250 VAC.This allows the use of Saf-D-Grid® in AC systems that require more power by increasing the wattage capability within the existing connector space.
SKU
2002G1
- Saf-D-Grid® 400 Flush Mount Receptacle Housing with snap-in panel mount for 0.8mm panel thickness.
- Flush snap-in panel mount design is compatible with crimp wire contacts.
- First Mate, Last Break ground contact provides the safety of an earthing path before engagement of the power contacts.
- The connectors are rated for current interruption for both electronic (capacitive) and electrical (resistive) loads.
- Passes UL & IEC finger probe (plug & receptacle) and 3mm probe tests (receptacle). Minimizes the risk of personal contact with a hazardous voltage.
- Housings contain the arc if connectors are mated or unmated while under load minimizing risk to personnel.
- Anderson Power Products®® has lead the connector industry in development of DC power connection solutions since the introduction of the SB® electrical connector in 1953. Saf-D-Grid® builds on the proven contact technology used in SB® and Powerpole® connectors by offering features required in 380-400VDC power distribution systems.
- APP® introduced the Saf-D-Grid® connector system in January 2009 as a safe appliance power connector for server, telecommunication, and other devices up to 600 VDC.
- The APP® Saf-D-Grid® plug and receptacle provide for thedirect connection of DC electronic devices to a DC micro-gridpowered by renewable energy or high efficiency DC sources.The connector meets international safety requirements for hazardous, low voltage applications including UL 950 and IEC60950. The Saf-D-Grid® is size compatible with the IEC 320C13 and C14 AC connection system. It is the only connector system so sized that is UL rated for disconnect of a 400 VDC,20 amp load.
- Saf-D-Grid® also enables greater power density by allowing up to 40A and 600V DC or AC within the same space of the IEC320 C13 & C14 system that is limited to 10A and 250 VAC.This allows the use of Saf-D-Grid® in AC systems that require more power by increasing the wattage capability within the existing connector space.
Customer Reviews
Specifications
ELECTRICAL | |
Voltage (AC/DC) | |
• UL 1977 / CSA 22.2 | 600 |
• IEC | 400 |
Current Rating (Amperes) | 40 |
Wire Range (AWG) | #12 to #18 |
(mm²) | 2.5 to 0.75 |
Hot Plug Rated | |
• 250 cycles | 400V @ 440A in-rush |
• 250 cycles (UL) | 400V @ 20A load |
Dielectric Withstanding Voltage | 3,300 |
Operating Temperature (°C) | -20° to 80° |
(°F) | -4° to 176° |
Fault Current Withstand | |
UL 467 | 14 AWG, 300A, 4 Sec. |
MECHANICAL | |
Contact Retention (lbf) | 20 |
(N) | 89 |
Plug Latch Retention (lbf) | 20 |
(N) | 89 |
Panel Latch Retention (lbf) | 60 |
(N) | 267 |
Durability | 5,000 cycles - no load |
Receptacle Max Wire OD (in) | 0.22 |
(mm) | 5.6 |
Creep & Clearance per UL & IEC 60950 | |
Between live parts of different polarity, | |
e arthing circuit and the mating surface. | |
• Short and Flush Receptacle | |
with Crimp Contacts | 8.0 mm |
• Ultra Short Receptacle, Short | 7.0 mm |
and Flush Receptacle with Solder | |
or PCB Contacts | |
Maximum PCB Thickness A (in) | 0.093 |
(mm) | 2.4 |
Mechanical Shock B | |
IEC 60512-4-6C | 50g’s |
Vibration, High Frequency B | |
IEC 60512-4-6d | 20g’s |
PROTECTION | |
Touch Safety with Connector Housing | |
IEC 60529 | IP20 |
MATERIALS | |
Housing | |
• 2006G1 Series Receptacles | Hi Temp Nylon + 30% GF, UL94 V-0, Halogen Free |
• All other Receptacles & Plugs | Polycarbonate UL94 V-0 |
Springs | Stainless Steel |
Contacts | Copper, Silver Plate |
Cable / Strain Relief | Thermoplastic UL94 V-2 |
A - Applicable only to receptacles intended for termination to PCB
B - Tested with straight plug and flush mount receptacle with #14 AWG wire and 2003G1
contacts.
Please
Login
to download items.
3D-Step
3D-IGS
- 2002G1-SDG-STD-REC-HSG-STEP.zip 2002G1-SDG-STD-REC-HSG-STEP.zip
- 2002G1-SDG-STD-REC-HSG-IGS.zip 2002G1-SDG-STD-REC-HSG-IGS.zip